1. What is “accessible” as applied to wiring methods?
Wiring that is readily available to inspection, repair, removal, etc., without disturbing the building structure or finish. Not permanently enclosed by the structure or finish of buildings.

2. What is “accessible” as applied to equipment?
Equipment that may be readily reached without climbing over obstacles or that is not in locked or other hard to reach areas. For example, panel boards in kitchen cabinets that are mounted in or on the walls above washers and dryers, or in closets or bath- rooms, are not accessible. Service-entrance equipment that can be reached only by going into a closet, behind a stairway, or around some other obstacle would not be considered accessible.

3. What does “ampacity” mean?
The amount of flowing current (in amperes) that a conductor can carry continuously for specific use conditions and not exceed the temperature rating of the conductor.

4. What does “dead front” mean?
No live (energized) parts are exposed where a person operates electrical equipment.

5. What does “approved” mean?
Any appliance, wiring material or other electrical equipment that is acceptable to the enforcing authorities.  Underwriters Laboratory is (by far) the most acceptable authority to inspectors.

6. What does “identified” mean as applied to equipment?
It means that the equipment will be suitable for the particular use or environment, that it has been evaluated by a qualified electrical testing organization, and that it features a product listing or label indicating its suitability.

7. What is a branch circuit?
A branch circuit is the portion of a wiring system that extends beyond the last overcurrent-protective device. In interpreting this, you must not consider the thermal cutout or the motor overload protection as the beginning of the branch circuit. The branch circuit actually begins at the final fusing or circuit-breaker point where the circuit breaks off to supply the motor.

8. What is a small appliance branch circuit?
This is the circuit supplying one or more outlets connecting appliances only. There is no permanently connected lighting on this circuit, except the lighting that may be built into an appliance. Refer to outlets for small appliance loads in kitchens, laundries, pantries, and dining and breakfast rooms of dwellings.

9. What is a general purpose circuit? This is a branch circuit to which lighting and/or appliances may be connected. 

10. What is a multiwire branch circuit?
A multiwire branch circuit has two or more ungrounded conductors with a potential difference between them and also has a grounded (neutral) conductor with an equal potential difference between it and each of the other wires. Examples are a three- wire 120/240-volt system or a 120/208-volt wye system, using two-or three-phase  conductors  and  a  grounded  conductor. However, in either case, the “hot” wires must not be tied to one phase but must be connected to different phases to make the system a multiwire circuit
 
11. What is a circuit breaker?
A device that is designed not only to open and close a circuit nonautomatically but also to open the circuit automatically at a predetermined current-overload value. The circuit breaker may be thermally or magnetically operated. However, ambient temperatures affect the operation of the thermally operated type, so that the trip value of the current is not as stable as with the magnetic type.

12. What is a current-carrying conductor?
A conductor that is expected to carry current under normal operating conditions.

13. What is a noncurrent-carrying conductor?
One that carries current only in the event of a malfunction of equipment or wiring. An equipment grounding conductor is a good example. It is employed for protection and is quite a necessary part of the wiring system, but it is not used to carry current except in the case of faulty operation, where it aids in tripping the overcurrent-protective device.

14. What is a pressure connector (solderless)?
A device that establishes a good electrical connection between two or more conductors by some means of mechanical pressure. A pressure connector is used in place of soldering connections and is required to be of an approved type.

15. What is meant by “demand factor”?
This is the ratio between the maximum demand on a system or part of a system and the total connected load on the same system or part of the system.

16. What is meant by “explosionproof apparatus”?
Apparatus enclosed in a case that is able to sustain an explosion that may occur within the case and is also able to prevent ignition of specified gases or vapors surrounding the enclosure caused by sparks, flashes, or explosion of the gases or vapors.

17. What is a feeder?
The circuit conductors between the service equipment, or the source of a separately derived system, and the final branch- circuit overcurrent device or devices. Generally, feeders are com- paratively large in size and supply a feeder panel, which is composed of a number of branch-circuit overcurrent devices.

18. What is a fitting?
A mechanical device, such as a locknut or bushing, that is intended primarily for a mechanical, rather than an electrical, function.

19. What is meant by a “ground”?
An  electrical  connection,  either  accidental  or  intentional, that exists between an electrical circuit or equipment and the earth, or some other conducting body that serves in place of the earth.

20. What does “grounded” mean?
Connected to the earth or to some other conducting body that serves in place of the earth.

21. What is a grounded conductor?
A system or circuit conductor that has been intentionally grounded.

22. What is a grounding conductor?
A conductor that is used to connect equipment, devices, or wiring systems with grounding electrodes.

23. What is a grounding conductor (equipment)?
The conductor used to connect noncurrent-carrying metal parts of equipment, raceways, and other enclosures to the system grounding conductor at the service and/or the grounding electrode conductor.

24. What is a grounding electrode conductor?
A conductor used to connect the grounding electrode to the equipment grounding conductor and/or to the grounded conductor of the circuit at the service.

25. What is a dwelling unit?
A dwelling unit includes one or more rooms used by one or more persons, with space for sleeping, eating, living, and a permanent provision for cooking and sanitation.

26. What is an outlet?
A point in the wiring system at which current is taken to supply some equipment.

 27. What is meant by “rain-tight”?
Capable of withstanding a beating rain without allowing water to enter.

28. What is a receptacle?
A receptacle is a contact device installed at the outlet for the connection of a single attachment plug. A single receptacle is a single device with no other contact device on the same yoke. A multiple receptacle is a single device containing two or more receptacles.

29. What does “rainproof” mean?
So constructed, protected, or treated as to prevent rain from interfering with the successful operation of the apparatus.

30. What is meant by the term “service”?
The  conductors  and  equipment  for  delivering  electrical energy from the secondary distribution system the street main, the distribution feeder, or the transformer to the wiring system on the premises. This includes the service entrance equipment and the grounding electrode. 

31. What are service conductors?
The  portion  of  the  supply  conductors  that  extend  from the  street main, duct, or transformers to the service-entrance equipment of the premises supplied. For overhead conductors, this includes the conductors from the last line pole (not including the service pole) to the service equipment.

32. What is a service cable?
A service conductor manufactured in the form of a cable and normally referred to as SE cable, or USE cable.
 
33. What is meant by “service drop”?
The overhead conductors from the last pole or other aerial support to and including the splices, if any, connecting to the service-entrance conductors at the building or other structure. If there is a service pole with a meter on it, such as a farm service pole, the service drop does not stop at the service pole; all wires extending from this pole to a building or buildings are service drops, as well as the conductors from the last line pole to the service pole.

34. What are service-entrance conductors (overhead system)?
That portion of the service conductors between the terminals of service equipment and a point outside the building, clear of building walls, where they are joined by a splice or tap to the ser- vice drop, street main, or other source of supply.

35. What are service-entrance conductors (underground system)?
The service conductors between the terminals of the service equipment and the point of connection to the service lateral. Where service equipment is located outside the building walls, there may be no service-entrance conductors, or they may be entirely outside the building.

36. What are sets of service-entrance conductors?
Sets of service-entrance conductors are taps that run from main service conductors to service equipment.

37. What is meant by “service equipment”?
The necessary equipment, usually consisting of circuit breakers or switches and fuses and their accessories, located near the point of where supply conductors enter a building, structure, or an otherwise defined area, and intended to constitute the main control and means to cut off the supply.

38. What is meant by “service lateral”?
The underground  service  conductors  between  the  street main, including any risers at the pole or other structure, or from transformers, and the first point of connection to the service- entrance conductors in a terminal box. The point of connection is considered to be the point where the service conductors enter the building.

39. What is meant by “service raceway”?
The rigid metal conduit, electrical metallic tubing, or other raceway that encloses service-entrance conductors.

40. What is meant by a “general-use switch”?
A device intended for use as a switch in general distribution and branch circuits. It is rated in amperes and is capable of interrupting its rated current at its rated voltage.

41. What is meant by a “T-rated switch”?
An AC general-use snap switch that can be used (a) on resistive and inductive loads that don’t exceed the ampere rating at the voltage involved, (b) on tungsten-filament lighting loads that don’t exceed the ampere rating at 120 volts, and (c) on motor loads that don’t exceed 80% of their ampere rating at the rated voltage.

42. What is meant by an “isolating switch”?
A switch that is intended to isolate an electric circuit from its source of power. It has no interrupting rating and is intended to be operated only after the circuit has been opened by some other means.

43. What is meant by a “motor-circuit switch”?
A switch, rated in horsepower, that is capable of interrupting the maximum operating overload current of a motor of the same horsepower rating as the switch, at the rated voltage.

44. What is meant by “watertight”?
So constructed that moisture won’t enter the enclosing case.

45. What is meant by “weatherproof”?
So constructed or protected that exposure to the weather won’t interfere with successful operation. Raintight or watertight may fulfill the requirements for “weatherproof.” However, weather conditions vary, and consideration should be given to conditions resulting from snow, ice, dust, and temperature extremes.

46. What is the percentage of allowable voltage drop for feeders that are used for power and heating loads?
Maximum of 3%.

47. What is the percentage of allowable voltage drop for feeders that are used for lighting loads? Maximum of 3%.
48. Give  some  examples  of  equipment  that  causes  inductive reactance.
Motors, transformers, choke coils, relay coils, ballasts.

49. When only inductive reactance is present in an ac circuit, what happens to the current in relation to the voltage?
The current is said to lag behind the voltage.

50. What is a preheated-type fluorescent tube?
There are two external contacts at each end of a glass tube. Each set of contacts is connected to a specially treated tungsten filament. The inside of the tube is coated with a fluorescent powder, the type of powder used controls the color output of the tube. The tube is filled with an inert gas, such as argon, and a small drop of mercury to facilitate starting.

51. What kind of light does the fluorescent bulb produce within the bulb itself?
Ultraviolet light.

52. Do the filaments stay lit during the operation of a fluorescent bulb? Explain.
No. They remain lit only at the start to vaporize the mercury; they are then shut off by the starter. Current is supplied to one contact on each end, thereby sustaining the mercury arc within the tube.

53. Is a fluorescent fixture more efficient than an incandescent fixture?
Yes. However, no fixed efficiency can be quoted because it varies with the size of the bulb, the ballast, etc. As a rule of thumb, a 40-watt fluorescent bulb is generally considered to put out about the same amount of light as a 100-watt incandescent bulb.

54. Does room temperature affect the operation of fluorescent lamps?
Yes. The normal fluorescent lamp is designed for operation at 50 F or higher.

55. If the operating temperature is expected to be below 50°F, what measures should be taken when using fluorescent lamps? Use special lamps and starters that are designed for lower temperatures.

56. Do fluorescent lamps produce a stroboscopic effect? Explain.
Yes. This effect is due to the fact that at 60 hertz the current passes through zero 120 times a second.

57. How can the strobe effect be compensated for in a two-bulb system?
When the power factor is corrected, the capacitor is so connected that at the instant the current in one bulb is passing through zero, the current in the other bulb is not at zero, and the strobe effect goes unnoticed.

58. What is another way to minimize the strobe effect?
By using a higher frequency, such as 400 hertz.

59. Does a 400-hertz frequency have any other advantages?
Yes. Smaller and lighter ballasts can be used. This makes it feasible to use simple capacitance-type ballasts, which produce an overall gain in efficiency.

60. Does frequent starting and stopping of fluorescent lighting affect the bulb life?
The life of fluorescent bulbs is affected by starting and stop- ping. A bulb that is constantly left on will have a much longer life than one that is turned on and off frequently.

61. When lighting an outdoor activity area with large incandescent bulbs, how can the light output of the bulbs be increased?
By using bulbs of a lower voltage rating than that of the source of supply. For example, by using a bulb that is rated at 105 volts on a 120-volt supply, the output can be increased by roughly 30%, but the life of the bulb will be cut by about 10%.

62. How is the light output of lamps rated?
In lumens.

63. How are light levels rated?
In foot-candles.

64. What is a foot-candle?
The amount of direct light emitted by one international can- dle on a square foot of surface, every part of which is one foot away.

65. Is the nec a law?
It is not a law, but it is adopted into laws that are established by governmental agencies; it may be adopted in its entirety, in part, or with amendments.

66. Who has the responsibility for Code interpretations?
The administrative authority that has jurisdiction over endorsement of the Code has the responsibility for making Code interpretations.
 
67. When are rules in the nec mandatory and when are they advisory?
When the word “shall” is used, the rules are mandatory.

68. According to the nec, what are voltages?
Throughout the Code, the voltage considered shall be that at which the circuit operates. This is often expressed as, for example, 600 volts, nominal.
 
69. When referring to conductors, what material is referred to?
Copper, unless otherwise specified. When other materials are to be used, the wire sizes must be changed accordingly.

70. In what manner must the work be executed?
All electrical equipment must be installed in a neat and work- manlike manner.

71. May  wooden  plugs  be  used  for  mounting  equipment  in masonry, concrete, plaster, etc.?
No.
 
72. How must conductors be spliced or joined together?
They must be spliced or joined together by approved splicing devices or by brazing, welding, or soldering with a fusible metal or alloy.
 
73. When soldering, what precautions must be used?
All  joints  or  splices  must  be  electrically  and  mechanically secure before soldering and then soldered with a noncorrosive flux This does not apply to conductors for grounding purposes; soldering is not allowed on these conductors.

74. How should splices or joints be insulated?
They must be covered with an insulation that is equivalent to the original conductor insulation.

75. Can an autotransformer be used on an ungrounded system?
The autotransformer must have a grounded conductor that is common to both primary and secondary circuits and tied into a grounded  conductor  on  the  system  supplying  the  autotransformer. An autotransformer may be used to extend or add an individual branch circuit in an existing installation for equipment load without the connection to a similar grounded conductor when transforming from a nominal 208-volt supply or similarly from 240 volts to 208 volts.

76. On No. 6 or smaller conductors, what means must be used for the identification of the grounded conductors?
Insulated  conductors  of  No.  6  or  smaller,  when  used  as grounded conductors, must be white, natural gray, or colored (but never green) with three longitudinal white stripes. On Type MI cable, the conductors must be distinctively marked at the terminal during installation.
 
77. How should conductors larger than No. 6 be marked to indicate the grounded wire?
By the use of white, natural gray, or colored (but never green) insulation with three longitudinal white stripes, or by identifying with a distinctive white marking at the terminals during installation.

78. How is the high-leg conductor of a 4-wire delta identified?
When the midpoint of one phase is grounded to supply lighting and similar loads on a 4wire delta-connected secondary, the phase conductor with the higher voltage to ground shall be orange in color or be indicated by tagging or other effective means at the point where a connection is to be made if the neutral conductor is present.

79. On a grounded system, which wire must be connected to the screw shell of a lampholder?
The grounded conductor.

80. What will determine the classification of branch circuits?
The maximum permitted setting or rating of the overcurrent- protective device in the circuit.

81. What color-coding is required on multiwire branch circuits?
The grounded conductor of a branch circuit shall be identified by a continuous white or natural gray color. Whenever conductors of different systems are installed in the same raceway, box, auxiliary gutter, or other types of enclosures, one system grounded conductor, if required, shall have an outer covering of white or natural gray. Each other system grounded conductor, if required, shall have an outer covering of white with an identifiable colored stripe (not green) running along the insulation or another means of identification. Ungrounded conductors of different voltages shall be a different color or identified by other means.

82. How must a conductor that is used only for equipment and grounding purposes be identified?
By the use of a green color, or green with one or more yellow stripes, or by being bare (only grounding conductors may be bare).

83. Can green-colored wire be used for circuit wires?
No.  Green  is  intended  for  identification  of  equipment- grounding conductors only.

84. What voltage is used between conductors that supply lamp- holders  of  the  screw-shell  type,  receptacles,  and  appliances  in dwellings?
Generally speaking, a voltage of 120 volts between conductors is considered the maximum. There are, however, some exceptions.

85. How must you ground the grounding terminal of a grounding- type receptacle?
By the use of an equipment-grounding conductor of green covered wire, green with one or more yellow stripes, or bare conductors. However, the armor of Type AC metal-clad cable, the sheath of MI cable, or a metallic raceway is acceptable as a grounding means. PEC does not permit the general use of flexible metal conduit as a grounding means unless it and the connectors are listed.

86. How can you ground the grounding terminal on a grounding- type receptacle on extensions to existing systems?
Run the grounding conductor to a grounded water pipe near the equipment.

87. What is the minimum size for branch-circuit conductors?
They cannot be smaller than No. 8 for ranges of 83⁄4   kW or higher rating and not smaller than No. 14 for other loads.

88. What is the requirement concerning all receptacles on 15- and 20-ampere branch circuits?
All receptacles on 15- and 20-ampere branch circuits must be of the grounding type. A single receptacle installed on an individual branch circuit must have a rating of not less than the rating of the branch circuit.

89. What are the requirements for spacing receptacles in dwelling occupancies?
All receptacles in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, sun rooms, recreation rooms, and bedrooms must be installed so that no point along the wall space, measured horizontally, is more than 6 feet from a receptacle. This includes wall space that is 2 feet or wider and any space occupied by  sliding  panels  on  exterior  walls.  Sliding  glass  panels  are excepted. At least one outlet must be installed for the laundry.
 
90. A  fastened-in-place  appliance  is  located  on  a  15-  or  20- ampere branch circuit on which there is a lighting fixture. What is the maximum rating that would be permitted on the appliance?
50 percent of the branch circuit rating.
 
91. A cord-and-plug-connected appliance is used on a 15- or 20- ampere branch circuit. What is the maximum rating permitted for the appliance?
80 percent of the branch circuit rating.
 
92. What is the smallest size wire permissible for a feeder circuit?
No. 10 wire.
 
93. What are the permissible voltage drops allowable on feeders and branch circuits?
On feeders, not more than 3 percent for power, heating, and lighting loads or combinations thereof, and a total maximum voltage drop not to exceed 5 percent for conductors and for combinations of feeders and branch circuits.
 
94. What is the basis for figuring the general lighting loads in occupancies?
They are figured on a volt-amperes-per-square-foot basis.

95. What measurements are used to determine the number of watts per square foot?
The outside dimensions of the building and the number of floors, not including open porches or garage.
 
96. What is the unit load per square foot (in volt-amperes) for a hospital?
2 volt-amperes.
 
97. What is the unit load per square foot (in volt-amperes) for a school?
3 volt-amperes.

98. How many volt-amperes per square foot are required to be included for general-purpose receptacle outlets when a set of plans does not show their locations in an office building?
1 volt-ampere per square foot.
 
99. What is the unit load per square foot (in volt-amperes) for a warehouse used for storage? 1⁄4  volt-ampere.

100. What voltages are used for purposes of computing feeder and branchcircuit loads when other voltages are not specified?
120, 120/240, 208Y/120, 240, 480Y/277, 480, and 600 volts.

101. How are continuous and noncontinuous loads for feeder ratings calculated?
Branch circuits must be rated no less than the noncontinuous load, plus at least 125 percent of the continuous load.
 
102. Are unfinished basements of dwellings used in figuring watts per square foot?
Yes, if adaptable for future use. If these spaces are not adaptable, they are not used.
 
103. What loads are used in figuring outlets for other than general illumination?
Outlets supplying specific loads and appliances must use the ampere rating of the appliance. Outlets supplying heavy-duty lampholders must use 600 voltamperes; calculations for other outlets must use 180 volt-amperes.
 
104. What load must be figured for show-window lighting?
Not less than 200 volt-amperes for each linear foot measured horizontally along the base.
 
105. What are the receptacle requirements in dwelling occupancies for kitchen, family room, laundry, pantry, dining room, and break- fast room?
There shall be a minimum of two 20-ampere small-appliance circuits for the kitchen, family room, pantry, dining room, and breakfast room. There should also be a minimum of one 20- ampere circuit for the laundry.

106. What is the unit load per square foot (in volt-amperes) for a store?
3 volt-amperes.

107. Outlets for heavy-duty lampholders are to be based on a load of how many volt-amperes?
600.
 
108. Are demand factors permitted in determining feeder loads?
Yes.

109. What size feeders must be installed in dwelling occupancies?
The computed load of a feeder must not be less than the sum of all branch circuit loads supplied by the feeder. The demand factors can be used in the calculation of feeder sizes.

110. When figuring the neutral load to electric ranges, what is the maximum unbalanced load considered to be?
The maximum unbalanced load for electric ranges is considered to be 70 percent of the load on the ungrounded conductors.

111. How is the neutral load on a 5-wire, 2-phase system deter- mined?
It is figured at 140 percent of the load on the ungrounded conductors.

112. How may the neutral-feeder load on a 3-wire dc or single- phase 3-wire ac system be determined?
The 70 percent demand factor may be used on range loads, and a further demand factor of 70 percent may be used on that portion of the unbalanced load in excess of 200 amperes.
 
113. How do you calculate the unbalanced load on a 4-wire, 3-phase system?
The 70 percent demand factor may be used on range loads, and a further demand factor of 70 percent may be used on that portion of the unbalanced load in excess of 200 amperes.

114. Can you make a reduction on the neutral feeder load where discharge lighting, data processing, or similar equipment is involved?
No reduction can be made on the neutral capacity for the portion of the load that consists of electric discharge lighting, data processing, or similar equipment. The load on the neutral feeder must be taken at 100 percent of the ungrounded conductors.
 
115. Why do discharge lighting loads require no reduction in neu- tral feeder capacity?
Because of the effect of the third harmonic on the current value in the neutral feeder. In fact, it’s sometimes necessary to oversize the neutral in such circuits. The same effect occurs when a great deal of data processing equipment is connected to the circuits.

116. Are demand factors applicable to electric ranges?
Yes.

117. Can demand factors be used on electric-clothes-dryer loads in the same manner as they are used on electric ranges?
Yes.
 
118. The demand factor for five household electric clothes dryers is calculated at what percentage?
80 percent.
 
119. Where two or more single-phase ranges are supplied by a 3-phase, 4-wire feeder, how is the total load computed?
On  the  basis  of  twice  the  maximum  number  connected between any two phases.

 120. What is the maximum demand for two household electric ranges, wallmounted ovens, counter-mounted cooking units, and other household cooking appliances rated at over 13⁄4  kW?
11 kW for ratings not over 12 kW.

121. What  computations  are  required  for  commercial  cooking equipment?
See nec, Table 220.20.

122. When computing the total load of a feeder for an electric heating system and an air-conditioning system that won’t be used simultaneously, must both loads be added?
No. The smaller of the two can be omitted.
 
123. What   are   the   minimum   requirements   for   service-drop conductors?
They  must  be  of  sufficient  size  to  carry  the  load  that  is required of them, but they musn’t be smaller than No. 8 copper wire or No. 6 aluminum, except under limited load conditions where they may not be smaller than No. 12 hard drawn copper.

124. What  is  the  minimum  clearance  for  service  drops  over buildings?
They shall have a minimum clearance of 8 feet . However, if the voltage does not exceed 300 volts between conductors and the roof has a slope of not less than 4 inches in 12 inches, the clearance may be a minimum of 3 feet.

125. What is the minimum height of point of attachment of service drops?
10 feet.

126. What is the minimum clearance of service drops over commercial areas, parking lots, agricultural areas, and other areas subject to truck traffic?
18 feet.
 
127. What is the minimum clearance of service drops over side- walks?
12 feet.
 
128. What is the minimum clearance of service drops over drive- ways, alleys, and public roads?
18 feet.
 
129. What is the minimum clearance of service drops over residential driveways?
12 feet.
 
130. Can a bare neutral conductor be buried in the ground in an underground service?
No; it must be insulated, unless it is in a duct or conduit .There is an exception: bare copper for direct burial where bare copper is judged to be suitable for the soil conditions.

 131. Where underground service conductors are carried up a pole, to what minimum height must they be given mechanical protection?
8 feet  132. Is sealing required where underground ducts or conduits enter buildings? Yes, to prevent the entrance of gases or moisture into the building. Spare or unused conduits and ducts must also be sealed.

133. What is the minimum size of service-entrance conductor normally allowed?
Any approved conductor having an ampacity equal to the sum of the noncontinuous loads, plus 125 percent of continuous loads. However, if the service entrance conductors terminate in an overcurrent device and assembly listed for operation at 100 percent of its rating, the 125 percent multiplier need not be used.

134. What is the minimum size service for a single-family dwelling with an initial load of 10 kVA or more? The service must be a minimum of 100 amperes for a 3-wire service  135. A residence has more than six 2-wire branch circuits. What is the minimum size of service required for this residence? The service entrance conductors shall have an ampacity of not less than 100 amperes for a 3-wire service.
 
136. Are splices permitted in service-entrance conductors?
Yes. They may be spliced with clamped or bolted connections; or buried splices may be made with a listed underground splice kit.

137. Are conductors other than service-entrance conductors permitted in the same raceways or cables?
No, except for grounding conductors and load management control conductors.
 
138. What must be provided for the disconnection of service conductors from building conductors? Some means must be provided for disconnecting all of the building conductors from the service-entrance conductors, and this means must be located in a readily accessible point nearest the point of entrance of the service conductors, on either the out- side or inside of the building, whichever is most convenient.

139. What must the service disconnecting means consist of?
It may consist of not more than six switches or six circuit breakers in a common enclosure or in a group of separate enclosures, provided that they are grouped together. Two or three single-pole switches or circuit breakers may be installed on multi- wire circuits and counted as one, provided they have handle ties or handles, so that not more than six operations of the hand are required to disconnect all circuits.
 
140. What may be connected ahead of the service entrance disconnecting switch?
Service fuses, meters, high-impedance shunt circuits (such as potential coils of meters), supply conductors for time switches, surge-protection capacitors, instrument transformers, lightning arresters, solar electric systems, interconnected electric power production sources, and circuits for emergency systems (such as fire-pump equipment, etc.)

141. In multiple-occupancy dwellings, must each occupant have access to his disconnecting means? Yes, except if the disconnects are under constant supervision and maintenance; in this case, they can be accessible to the building management only.
 
142. Is it permissible to install overcurrent-protective devices in the grounded service conductor? Overcurrent-protective devices may not be installed in the grounded service conductor unless a circuit breaker is used.

143. What is the minimum size of service-entrance conductors operating at over 600 volts?
They musn’t be smaller than No. 6 wire, unless in cable, where they may be a minimum of No. 8.
 
144. What is the maximum circuit protection allowed with flexible cords, sizes No. 16 or No. 18, and tinsel cord?
30 and 20 amperes.
 
145. What is the maximum overcurrent protection allowed on cords of 20 amperes capacity?
50 amperes.

146. Give the standard ratings (in amperes) for fuses and circuit breakers.
Standard ratings are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000

147. Where  can  an  overcurrent  device  be  used  in  a  grounded conductor?
No overcurrent device shall be placed in any permanently grounded conductor, except as follows: Where the overcurrent device simultaneously opens all conductors of the circuit . A fuse shall also be inserted in the grounded conductor when the supply is  3wire,  3-phase  ac,  one  conductor  grounded 

148. May fuses be arranged in parallel?
No, except as factory assembled in parallel and approved as a unit.

 149. May breakers be paralleled?
No, only circuit breakers assembled in parallel that are tested and approved as a single unit.
 
150. Are  the  secondary  conductors  of  transformer  feeder  taps required to have overcurrent protection?
Yes.

151. In what position must a knife switch with fuses be mounted? Why?
In a vertical position, so that when the switch is opened, the blades won’t close by gravity; the line side must be connected so that when the switch is opened, the fuses will be deenergized.
 
152. When overcurrent-protective device enclosures are mounted in a damp location, what precautions must be taken?
The enclosures must be of an identified type for the location and must be mounted with at least a 1⁄4-inch air space between the wall or supporting surface.
 
153. Where may Edison-base plug fuses be used?
Plug fuses of the Edison-base type shall be used only for replacement in existing installations where there is no evidence of overfusing or tampering.
 
154. What is the maximum voltage rating of plug fuses?
125 volts.
 
155. What precautions must be taken if plug fuses are used on new installations?
Fuses,   fuseholders,   and   adapters   must   be   so   designed that  other Type S fuses may not be used.

156. What are the size classifications of Type S fuses and adapters?
Not exceeding 125 volts at 0–15 amperes, 16–20 amperes, and 21–30 amperes.
 
157. What is a Type S fuse?
A dual element fuse with special threads so that fuses larger than what the circuit was designed for may not be used. They are designed to make tampering or bridging difficult.

158. Why are systems and circuits grounded?
To limit the excess voltage to ground, which might occur from lightning or exposure to other higher-voltage sources.

159. Is it necessary to ground one wire on a two-wire dc system with not more than 300 volts between conductors?
Yes, in practically every case, although there are a few exceptions.

 160. When should ac systems be grounded?
AC circuits and systems must be grounded.
 
161. When is the next higher overcurrent protective device permit- ted to protect a conductor where a standard fuse or circuit breaker is not available?
In general up to 800 amperes.
 
162. When do circuits of 50 volts or less to ground have to be grounded?
When do they not have to be grounded? Circuits of less than 50 volts need not be grounded unless they are supplied from systems exceeding 150 volts to ground, where they are supplied by transformers from ungrounded systems, or where they run overhead outside buildings.

163. If a grounded conductor is not going to be used in a building, must this grounded conductor be run to each service?
Yes. The grounded conductor must be run to each service. It need not be taken farther than the service equipment if it won’t be required in any of the circuits.

164. Is  it  necessary  to  ground  each  service  on  a  grounded  ac system?
Each individual service must have a ground, and this ground must be connected on the supply side of the service-disconnecting means. If there is only one service from a transformer, there must be additional ground connection at the transformer or elsewhere in the transformer circuit for the installation to be approved.
 
165. What are the grounding requirements when two or more buildings are supplied from one service?
Where two or more buildings or structures are supplied from a common service, the grounded system in each building or structure is required to have a grounded electrode as described in PEC, connected to the metal enclosure of the building disconnecting means and to the ac system grounded circuit conductor on the supply side of the building or structure disconnecting means.
 
166. Is it required to ground a separately derived system, and if so, where?
Premises wiring systems that are required by PEC to be grounded shall be grounded if the phase conductors are not physically connected to another supply system. They shall be grounded at the transformer, generator, or other source of sup- ply, or at the switchboard on the supply side of the disconnecting means.
 
167. When must metal, noncurrent-carrying parts of fixed equipment that are likely to become energized be grounded?
When supplied by metal-clad wiring, when located in damp or wet places, when within reach of a person who can make con- tact with a grounded surface or object or within reach of a person standing on the ground, when in hazardous locations, or where any switches, enclosures, etc., are accessible to unqualified persons.
 
168. Must metal buildings be grounded?
If excessive metal in or on buildings may become energized and  is  subject  to  personal  contact,  adequate  bonding  and grounding  will  provide  additional  safety.
 
169. What is the exception to grounding the noncurrent-carrying parts of portable tools and appliances?
Portable tools and appliances may have double insulation. If they have, they must be so marked and won’t require grounding.
 
170. What are the grounding requirements when lightning rods and conductors are present?
Lightning protection ground terminals must be bonded to the building’s grounding system. In addition, metal enclosures with conductors should be kept at least 6 feet away from lightning conductors. Where this is not practical, they must be bonded together. However, this 6-foot rule is a Fine Print Note and not a requirement  of  the  nec.
 
171. What is meant by effective grounding?
The path to ground must be permanent and continuous, must be capable of safely handling the currents that may be imposed on the ground, and must have sufficiently low impedance to limit the potential above ground to facilitate the opening of the overcurrent devices. The earth may not be used as the only equipment-grounding conductor.
 
172. What is a grounding electrode conductor used for?
The grounding conductor for circuits is used for grounding equipment, conduit, and other metal raceways, including service conduit, cable sheath, etc.

7-54 What appliances may be grounded to the neutral conductor?
Electric ranges and electric clothes dryers, provided that the neutral is not smaller than No. 10 copper wire . However, this is not allowed for equipment that is fed from feeder panels, in mobile homes, or in recreational vehicles.

173. Three-wire SE cable with a bare neutral is sometimes used for connecting ranges and dryers. Is it permissible to use this type of cable when the branch circuit originates from a feeder panel?
No.  The  neutral  must  be  insulated.
 
174. What equipment, other than electric ranges and clothes dryers, may be grounded to the grounding conductor?
The grounding conductor on the supply side of the service- disconnecting means may ground the equipment, meter housing, etc. The load side of the disconnecting means cannot be used for grounding any equipment other than electric ranges and dryers.
 
175. How should continuity at service equipment be assured?
Threaded couplings and bosses, as well as threadless couplings and connections in rigid conduit or EMT (electrical metallic tubing), must be wrenchtight. Bonding jumpers must be used around concentric and eccentric knockouts and ordinary lock- nuts and bushings cannot be used for bonding 
176. On flush-mounted grounded-type receptacles, is it necessary to bond the green grounding screw of the receptacle to the equipment ground?
Yes, with a few exceptions.
 
177. Can conduit serve as the equipment ground?
Except for a few cases, such as special precautions in hazardous locations, conduit, armored cable, metal raceways, etc., can serve as the equipment ground.
 
178. What is the preferred type of grounding electrode?
A metal underground water system where there are 10 feet or more  of  buried  metal  pipe,  including  well  casings  that  are bonded to the system, is the preferred grounding electrode .A made electrode shall also be used in addition to the buried metal water pipe.

179. What is a “made” electrode?
A made grounding electrode may be a driven pipe, driven rod, buried plate, or other metal underground system approved for the purpose of grounding the equipment.
 
180. What are the requirements for plate electrodes?
They musn’t have less than 2 square feet (.186 square meter) of surface exposed to the soil. Electrodes of iron or steel must be at least 1⁄4   inch (6.4mm) thick; if made of nonferrous metal, it must be at least 0.06 inch (1.5mm) thick.

181. What should be the resistance of made electrodes?
If a single made electrode does not measure a resistance to ground of 25 ohms or less, it must be supplemented by another electrode that is not less than 6 feet away from the first electrode 
182. May grounding electrode conductors be spliced? No, splices are not permitted; grounding electrode conductors must be one piece for their entire length, although there are some exceptions.
 
183. What  is  the  smallest  size  grounding  electrode  conductor permissible?
No. 4 wire or larger may be attached to buildings; No. 6 wire may be used if properly stapled to prevent physical damage; and No. 8 wire may be used if in conduit or armored cable for protection.
 
184. When a grounding electrode conductor is enclosed in a metal enclosure, how is the metal enclosure to be installed?
It must be electrically continuous from point of attachment to cabinet or enclosure to the point of attachment to the ground clamp or fitting. Metal enclosures that are not physically and electrically continuous must be bonded to the grounding elec- trode conductor at both ends of the metal enclosure.
 
185. May aluminum be used for a grounding electrode conductor?
Yes, but it may not come in contact with masonry or the earth and cannot be run closer than 18 inches from the earth.
 
186. If a water pipe is used as the grounding electrode, what precautions must be taken?
The grounding connection should be made at the point of water-service entrance. If this cannot be done and there is a water meter on the premises, the water meter must be bonded with a jumper of sufficient length, so that the water meter may be readily  removed  without  disturbing  the  bonding.  The  cold-water piping must be used, and it should be checked to make certain that there are no insulated connections in the piping.

187. Where nonmetallic water pipe serves an apartment building, what grounding procedures are recommended?
The ground must also be bonded to the interior metal water piping system, including the hot-water piping, and also to the sewer, gas piping, air tracts, etc. This will provide additional safety.

188. When reinforcing bar is used as the grounding electrode, are clamps required to be listed for connecting the grounding conductor to the rebar?
Yes. Exothermic welding is also permitted.
 
189. Can solder be used to attach connections to the grounding conductor?
Solder is never permitted; exothermic welding or listed pres- sure connectors are to be used.
 
190. What means must be taken to maintain continuity at metal boxes when nonmetallic systems of wiring are used so that the equipment ground wire will be continuous?
The equipment grounds must be attached by means of a grounding screw (boxes are now available with a tapped hole having 10/32 threads) or by some other listed means.
 
191. Are sheet-metal straps considered adequate for grounding a telephone system?
Yes, if attached to a rigid metal base that is seated on the water pipe or other ground electrode and listed for the purpose.

192. What special precautions must be taken in the use of ground clamps? They must be made of a material suitable for use in connection with the materials that they are attaching to because electrolysis may occur if they are made of different metals. All surfaces must be clean and free of paint or corrosion.

193. May aluminum grounding conductors be run to cold water piping?
Yes, but any clamps used with aluminum grounding conductors  must  be  approved  for  the  purpose.
 
194. May conductors of different systems occupy the same enclosure?
Conductors for light and power systems of 600 volts or less may occupy the same enclosure. The individual circuits may be  ac or dc, but the conductors must all be insulated for the maximum voltage of any conductor in the enclosure except emergency systems.
 
195. May conductors of systems over 600 volts occupy the same enclosure as conductors carrying less than 600 volts?
Under certain conditions.
 
196. If the secondary voltage on electric-discharge lamps is 1000 volts or less, may its wiring occupy the same fixture enclosure as the branch-circuit conductors?
Yes, if insulated for the secondary voltage involved.

197. Is it permissible to run control, relay, or ammeter conductors that are used in connection with a motor or starter in the same enclosure as the motor-circuit conductors?
Yes, if the insulation of all the conductors is enough for the highest voltage encountered.
 
198. When boxes, fittings, conduit, etc., are used in damp or corrosive places, how must they be protected?
They must be protected by a coating of approved corrosion- resistant material.
 
199. In damp locations, what precautions must be taken against the corrosion of boxes, fitting, conduit, etc.?
There must be an air space of at least 1  inch between the wall 4 or supporting material and any surface-mounted conduit fittings, etc.
 
200. When raceways extend from an area of one temperature into an area of a widely different temperature, what precautions must be taken?
Precautions must be taken to prevent the circulation of air from a warmer to a colder section through the raceway.
 
201. When raceways and conductors are run through studs, joints, and/or rafters, what precautions must be taken?
They should be run near the appropriate center of the wood members or at least 11⁄4  inches from the nearest edge; if the members  have  to  be  notched  or  a  11⁄4-inch  protection  cannot  be given, the conduit or conductors must be covered by a steel plate not less than 1/6 inch in thickness.
 
202. How much wire must be allowed at outlets and switch boxes for connections and splices?
There must be at least 6 inches of free conductor left for making the connections . It is a good practice, however, to leave more than 6 inches of free conductor at each box.

203. What precautions must be taken to prevent induced currents in metal enclosures?
When conductors carry ac, all phase wires and the neutral wire, if one is used, and all equipment grounding conductors must run in the same raceway. When single conductors must be passed through metal having magnetic properties (iron and steel), slotting the metal between the holes will help keep down the inductive effect.

204. When it is necessary to run wires through air-handling ducts or plenums, what precautions must be taken?
The conductors must be run in conduit, electrical metallic tubing, intermediate metal conduit, flexible steel conduit with lead-covered conductors, metal-clad cable, Type MI cable, inter- mediate metal conduit, or in a Plenum-rated cable.
 
205. Does temporary wiring, such as for construction, Christmas lighting, carnivals, etc., come under the PEC?
Yes.
 
206. Are ground-fault circuit interrupters required on temporary wiring for construction sites?
Yes, on all 15- and 20-ampere branch circuits.

207. When conductors are used underground in concrete slabs or other masonry that comes in direct contact with the earth, or where Condensation or accumulated moisture in raceways is apt to occur, what characteristic must the insulation have? It must be suitable for use in a wet location.
 
208. Name some insulations permitted for use in a wet location.
RHW, TW, THW, THWN, and XHHW type cable.

209. What are the cable requirements for buried conductors?
Cables of one or more conductors for direct burial in the earth must be Type USE cable, except for branch circuits and feeders, which may use Type UF cable. Type UF cable cannot be used for service wires.

210. What other rules apply to buried conductors?
All conductors, including the neutral, must be buried in the same trench and be continuous (without any splice).  Extra mechanical protection may be required, such as a covering board, concrete pad, or raceway.

211. What is the minimum size of conductors allowed by the PEC?
For power work, the smallest size is No. 14. However, smaller sizes are allowed for controls and in special circumstances.
 
212. What is the ruling on stranded conductors?
Except for bus bars, Type MI cable, and pool bonding, conductors of No. 8 and larger must be stranded.
 
213. What is the minimum size of conductors that may be paralleled?
Conductors in sizes 1/0 and larger may be run in multiple, though there are exceptions.
 
214. When conductors are run in parallel, what factors must be considered?
Each phase or neutral, if used, must be the same length and of the same conductor material; have the same circular-mil area and the same type of insulation; and be arranged to terminate at both ends so that there will be equal distribution of current between the conductors. Phases must be coordinated to eliminate Any induction currents that may be caused to flow in the raceways.
 
215. How many conductors may be run in raceways or cables without having to apply a derating factor to the current-carrying capacity?
Three current-carrying conductors (neutrals not included); when more than three current-carrying conductors are run, a derating factor must be applied.
 
216. What are the derating factors for more than three current- carrying conductors in raceways or cables?
4 to 6 conductors 80% rating 7 to 9 conductors 70% rating 10 to 24 conductors 70% rating 25 to 42 conductors 60% rating 43 conductors and above 50% rating.

 217. In derating, how is the neutral conductor considered?
Normally, the current in the neutral conductor is only the unbalanced current. Therefore, if the system is well balanced, the neutral is not considered as a current-carrying conductor and would not enter into derating.

218. In determining the current in the neutral conductor of a wye system, how is the neutral classed? In  a  4-wire,  3-phase,  wyes-connected  system,  a  common conductor carries approximately the same current as the other conductors and is therefore not considered a neutral in determining the derating of current capacity.

219. What size must the conductors be for a parallel feeder or service?
At least 1/0 and larger for aluminum, copper-clad aluminum, or copper conductors.
 
220. What are the minimum sizes for conductors when operated at a voltage of 0 through 2000 volts? No. 14 copper, No. 12 aluminum or copper-clad aluminum, with exceptions.
 
221. Where installed in raceways, stranded conductors of what size must be used?
No. 8 and larger.

222. What are the temperature limitations of conductors?
  60-75 Degrees  C.

223. What are the principal determinants of conductor operating temperatures?
The maximum temperature that the conductor can with- stand over a prolonged period of time without serious degradation.
 
224. How are grounded conductors identified?
They must be white or natural gray in color.

225. How are equipment grounding conductors identified?
They must be green, green with a yellow stripe, or bare.

226. How are ungrounded conductors identified?
They must be distinguished by colors other than white, gray, or green.

227. What does the term “electrical ducts” mean?
Suitable electrical raceways, run underground and embedded in concrete or earth.
 
228. What is the ampacity of a No. 6 AWG copper type THW conductor?
65 amperes.
 
229. What are the ampacity correction factors for a Type ac cable assembly when the ambient temperature is other than 30ºC (86ºF)?
Temperature rating of conductor 60°C (1.22), 75°C (1.13), 90ºC (1.10), 150ºC (1.04), 200ºC (1.03), 250ºC (1.02)

230. What is the maximum operating temperature for a Type THWN conductor?
75ºC (167ºF) in wet locations  2.

31. Under what conditions can a Type XHHW conductor are used in a wet location?
When it is rated at a temperature of 75ºC (167ºF).
 
232. What are the requirements when more than one calculated or tabulated ampacity could apply for a given circuit length?
The lowest value shall be used.
 
233. Give the ampacities for Types ac or NM conductor assemblies based on an ambient air temperature of 30ºC (86ºF).

234. What advantages would two parallel 500-MCM cables have over one 1000-MCM cable?
They would be easier to handle and to pull into raceways. According to PEC, RH wire has a current-carrying capacity of 545 amperes, whereas 500-MCM cable has a current-carrying capacity of 380 amperes. Therefore, two 500-MCM cables in parallel would have the same circular-mil area as one 1000-MCM cable and a current-carrying capacity of 760 amperes compared to the 545-ampere current-carrying capacity of one 1000-MCM cable. This is approximately 40 percent more current-carrying capacity for the two 500-MCM cables. In addition, there is usually a cost advantage by using two 500-MCM conductors, rather than one 1000-MCM conductor.

235. May THW insulated conductors be run through a continuous row of fluorescent fixtures?
Yes. 

236. Are cable trays intended to be used with ordinary branch circuit conductor?
No. They are not intended for this purpose.
 
237. Do cable trays have to be used as a complete system, or may they be used as only partial cable supports?
They must be used as a complete system, including boxes and fittings

238. Is grounding required on metallic cable trays?
They must be grounded but must not be used as the neutral conductor. If used as the equipment-grounding conductor, they must meet the requirements of PEC.

239. Is open wiring on insulators, commonly known as knob-and- tube wiring, recognized by the Code?
Yes, although it is almost never approved by inspectors for new installations. It is in the PEC primarily because a great deal of it has been previously installed and must be properly maintained 

240. What is Type MI cable?
Type MI cable is a cable in which one or more electrical conductors are insulated with a highly compressed refractory mineral insulation (magnesium oxide) and enclosed in a liquid-tight and gas-tight metallic sheathing (copper).

241. Where can Type MI cable be used?
This is one wiring material that can be used for practically every conceivable type of service or circuit. When it is exposed to cinder fill or other destructive corrosive conditions, it must be protected by materials suitable for these conditions.

242. What precautions must be taken with Type MI cable to pre- vent the entrance of moisture? Where Type MI cable terminates, an approved seal must be provided immediately after stripping to prevent the entrance of moisture into the mineral insulation; the conductors must be insulated with an approved insulation where they extend beyond the sheath.

243. Does the outer sheath of Type MI cable meet the requirements for equipment grounding?
Yes. It provides an excellent path for equipment grounding purposes but not for use as a grounded or neutral conductor.

244. What is armored cable commonly called?
Type AC cable, or in some locations “BX,” a name taken from the Bronx Cable Company.
 
245. What is metal-clad cable commonly called?
Type MC cable.
 
246. What is Type MC cable?
Type MC cables are power and control cables in the size range from No. 14 and larger for copper and No. 12 and larger for aluminum and copper-clad aluminum. The metal enclosures are either a covering of interlocking metal tape or a smooth, impervious, close-fitting, or corrugated tube. Supplemental protection of an outer covering of corrosion- resistant material is required where such protection is needed.

247. What is Type AC cable?
Type AC cables are branch-circuit and feeder cables with an armor of flexible metal tape. Cable of the AC type must have an internal bonding strip of copper or aluminum in tight physical con- tact with the armor for its entire length.
 
248. At what intervals must Type MC cable be supported?
At intervals not exceeding 6 feet.
 
249. At what intervals must Type AC cable be supported?
At intervals of not more than 41⁄4    feet and within 12 inches of boxes and fittings, except where cable is fished and except lengths of not over 2 feet at terminals where flexibility.
 
250. How may bends be made in Type AC cable?
Bends must be made so that the cables are not damaged. The radius of the curve of the inner edge of any bend must not be less than 5 times the diameter of Type AC cable.
 
251. What extra precaution is necessary with Type AC cable when attaching fittings?
An approved insulating bushing or equivalent approved protection must be provided between the conductors and the armor.
 
252. What is nonmetallic-sheathed cable?
Nonmetallic-sheathed cable is an assembly of two or more insulated  conductors  having  an  outer  sheath  of  moisture- resistant,  flame-retardant,  nonmetallic  material.
 
253. What are the available sizes of nonmetallic-sheathed cable?
Sizes No. 14 to No. 2 (AWG) inclusive.
 
254. What is the difference between Type NM and Type NMC? Cables?
In addition to having flame-retardant and moisture-resistant covering, Type NMC cable must also be fungus-resistant and corrosion-resistant.
 
255. Where may Type NM cable be used?
It may be used for exposed and concealed work in normally dry locations. It may also be installed or fished in the air voids of masonry block or tile walls, where such walls are not exposed to excessive moisture or dampness.
 
256. In dwelling occupancies, what, if any, restrictions have been added?
Types NM and NMC cables are permitted in one- and two- family dwellings or multifamily dwellings and other structures not  exceeding  three  floors  above  grade.
 
257. Where may Type NMC cable be installed?
Where exposed to corrosive fumes or vapors, for exposed and concealed work, in dry and moist or damp places, and inside or outside of masonry block or tile walls.

 258. Where is it not permissible to use Type NM or Type NMC? cable?
As service-entrance cable, in commercial garages, in theaters, and similar locations, except as provided in the PEC, Article 518, “Places of Assembly”.
 
259. What supports are necessary for Types NM and NMC cable?
The installation must not be subject to damage, and the cable must be secured in place at intervals not exceeding 41⁄2  feet and supported within 12 inches from boxes and fittings.
 
260. What are the two types of service-entrance cable?
Type SE and Type USE.
 
261. What type of outer sheath does a Type SE cable have?
It  has  a  flame-retardant,  moisture-resistant  covering.
 
262. What type of outer sheath does Type USE cable have?
For underground use, it has a moisture-resistant covering but is not required to have a flame-retardant covering.

263. Can service-entrance cable be used as branch-circuit conductors or feeder conductors?
It may be used for interior wiring systems only when all circuit conductors of the cable are of the thermoplastic or rubber type. However, service-entrance cable without individual insulation on the grounded (neutral) conductor can be used to sup- ply ranges or clothes dryers when the cable does not have an outer  metallic  covering  and  does  not  exceed  150  volts  to ground. It may also be used as a feeder when it supplies other buildings on the same premises. SE cable with a bare neutral must not originate in a feeder panel.

264. Describe underground feeder and branch-circuit cable.
Underground  feeder  and  branch-circuit  cable  must  be  an approved Type UF cable in sizes No. 14 copper or No. 12 aluminum or copper-clad aluminum to No. 4 0 AWG, inclusive. The ampacity of Type UF cable shall be that of 60ºC (140ºF) conductors in accordance with PEC. In addition, the cable can include a bare conductor for equipment grounding purposes only. The overall covering must also be suitable for direct burial in the earth.
 
265. What is required as overcurrent protection for Type UF cable?
Underground feeder and branch-circuit cable may be used underground, including direct burial, provided they have over- current protection that does not exceed the capacity of the conductors 
266. May conductors of the same circuit be run in separate trenches? All conductors of the same circuit must be run in the same trench or raceway.
 
267. What depth must UF cable be buried?
In general, UF cable must be buried at a depth of 24 inches or more. However, there are circumstances under which it can be buried at lesser depths.
 
268. May UF cable be used for interior wiring?
Yes, but it must be installed in accordance with Article 334 and must not be exposed to direct sunlight unless it is specifically identified for this purpose.
 
269. Where can rigid metal conduit are used?
Practically everywhere; however, rigid metal conduit protected solely by enamel cannot be used outdoors. Also, where practicable, dissimilar metals should not come in contact anywhere in the system to avoid the possibility of galvanic action, which could prove destructive to the system.
 
270. When subject to cinder fill, what precautions must be taken with rigid metal conduit?
It must be protected by a minimum of 2 inches of noncinder concrete.
 
271. What is the minimum size of rigid metal conduit?
1⁄2-inch trade size, with a few exceptions.
 
272. What  are  the  requirements  for  couplings  on  rigid  metal conduit?
Threaded or threadless couplings and connectors must be made tight. Where installed in wet locations or buried in concrete masonry or fill, the type used must prevent water from entering the conduit.
 
273. Are running threads permitted on rigid metal conduit?
They cannot be used on conduit for connections at couplings.

274. What is the maximum number of bends permitted in rigid metal conduit between outlets?
Not more than 4 quarter bends, or a total of 360º; this includes offsets, etc., at outlets and fittings.
 
275. After a cut is made in rigid metal conduit, what precaution must be taken?
All cut ends of conduits must be reamed to remove any rough ends that might damage the wire when it is pulled in.
 
276. What are the principal determinants of conductor operating temperatures?
The maximum temperature that the conductor can withstand over a prolonged period of time without serious degradation.
 
277. How are grounded conductors identified?
They must be white or natural gray in color.
 
278. How are equipment grounding conductors identified?
They must be green, green with a yellow stripe, or bare.
 
279. How are ungrounded conductors identified?
They must be distinguished by colors other than white, gray, or green.
 
280. What does the term “electrical ducts” mean?
Suitable electrical raceways run underground and embedded in concrete or earth.
 
281. What are the requirements when more than one calculated or tabulated ampacity could apply for a given circuit length?
The lowest value shall be used.

282. What is intermediate metal conduit?
It is a metal conduit, similar to rigid metal conduit, but slightly lighter weight.
 
283. What precautions should be taken when installing rigid non- metallic conduit in extreme cold? They should not be used in areas where they will be subjected to damage, since they can become brittle at low temperatures.

284. May plastic water pipe be used as conduit?
No. It may not be used for this purpose.
 
285. What uses are permitted for rigid nonmetallic conduit?
For 600 volts or less, except for direct burial where it is not less than 18 inches below grade and where the voltage exceeds 600 volts, in which case it must be encased in 2 inches of concrete; in concrete walls, floors, and ceilings; in locations subject to severe corrosive influences; in cinder fill; and in wet locations.

286. Where is the use of nonmetallic rigid conduit prohibited?
In hazardous locations, for the support of fixtures or other equipment, where subject to physical damage, or where high temperatures are present.
 
287. Where must expansion joints is used on rigid nonmetallic conduit?
Where required to compensate for thermal expansion and con- traction when the expansion.

288. Are bushings required when rigid nonmetallic conduit is used?
Yes.
 
289. What is electrical metallic tubing (EMT)?
A thin-walled metal raceway.
 
290. May more or fewer conductors be contained in EMT than in rigid metal conduit?
The same number of wires applies to both raceways.
 
291. When EMT is exposed to moisture or used outdoors, what types of fittings must be used?
They must be rain-tight fittings.
 
292. When EMT is buried in concrete, what type fittings must be used?
They must be concrete-tight fittings.
 
293. What is the maximum number of conductors permitted in metal wireways, and what is the maximum percentage of fill?
The maximum fill cannot exceed 20 percent of the interior cross-sectional area. A maximum of 30 current-carrying conductors  at  any  cross  section  (unless  derated);  signal  circuits  or starter-control wires are not included.
 
294. Are splices permitted in wireways?
Yes, provided that the conductors with splices do not take up more than 75 percent of the area of the wireway at any point.

295. May the wireways be open at the ends?
No. The dead ends must be closed.
 
296. Is the equipment-grounding conductor used in figuring the number of conductors allowed in a box?
Yes, but only one conductor is to be counted.
 
297. What is the purpose of auxiliary gutters?
They are used to supplement wiring spaces at meter centers, distribution centers, switchboards, and similar points of wiring systems; they may enclose conductors or bus bars but cannot be used to enclose switches, overcurrent devices, or other appliances or apparatuses.
 
298. What is the maximum number of conductors permitted in auxiliary  gutters,  and  what  is  the  maximum  percentage  of  fill allowed?
The maximum fill cannot exceed 20 percent of the interior cross-sectional area. A maximum of 30 current-carrying conductors at any cross section (unless dated); signal circuits or starter-control wires are not included.
 
299. What is the current-carrying capacity of bus bars in auxiliary gutters?
The current carried continuously in bare copper bars in auxiliary gutters shall not exceed 1000 amperes per square inch of cross section of the conductor. For aluminum bars the current carried continuously shall not exceed 700 amperes per square inch of cross section of the conductor 
300. May taps and splices be made in auxiliary gutters? Yes; however, splices may not occupy more than 75 percent of the crosssectional area at any point. All taps must be identified as to the circuit or equipment that they supply.
 
301. May round boxes be used as outlet, switch, or junction boxes?
No. They cannot be used where conduits or connectors with locknuts or bushings are used.
 
302. What are the requirements for pendant boxes?
Pendant boxes must be supported by either multiconductor cords or cables in an approved manner, or by conduit.

303. Can a box be used to support a ceiling fan?
Yes.

304. What protection must be given to conductors entering boxes or fittings?
They must be protected from abrasion, and the openings through which conductors enter must be adequately closed.

305. In what position must knife switches be mounted?
Single-throw knife switches must be mounted so that gravity won’t tend to close them. Double-throw knife switches may be mounted either vertically or horizontally; however, if mounted vertically, a locking device must be provided to ensure that the blades  remain  in  the  open  position  when  so  set.
 
306. Do switches and circuit breakers have to be accessible and grouped?
Yes. Switches and circuit breakers, as far as is practical, must be readily accessible.
 
307. What is the maximum number of overcurrent devices permitted on one panel board?
Not more than 42 overcurrent devices of a lighting and appliance branch-circuit panel board can be installed in any one cabinet or cutout box. A two-pole circuit breaker is considered as two overcurrent devices, and a three-pole circuit breaker is considered as three overcurrent devices in the interpretation of the question.
 
308. How would you define a lighting and appliance branch- circuit panel board?
A branch-circuit panel board that has more than 10 percent of  its  overcurrent  devices  rated  30  amps  or  less.
 
309. What methods are specified in the Code for protecting conductors in trenches from damage due to ground movement?
Coiling the conductor or cable.
 
8-136  Must all underground metal conduit and fittings be grounded?
Generally yes, but an exception is made for a metal conduit elbow in a rigid nonmetallic conduit run, if it is no less than 18 inches below grade, or if it is beneath a 4-inchthick concrete slab.

310. What is a primary cell?
A primary cell is a cell that produces electric current from an electrochemical reaction but is not capable of being recharged.

311. What is a secondary cell?
A cell that is capable of being recharged by passing an electric current through it in the opposite direction from the discharging current.

312. How are automobile batteries rated?
In ampere-hours.

313. Explain the meaning of ampere-hours.
At full charge, the battery is capable of delivering x number of amperes for y number of hours; e.g., a 100-ampere-hour battery would be capable of delivering 10 amperes for 10 hours, 1 ampere for 100 hours, etc.

314. When adding water to a car battery, what precautions should be observed?
Use distilled water only, and fill the cells only to their pre- scribed levels.

315. Will a discharged car battery freeze easier than a fully charged battery?
Yes.

316. How can a lead-acid battery be recharged?
By connecting it to a dc source at slightly higher than battery voltage and passing a high current through it in the opposite direction from the discharging current.

317. What derating factors must be applied to a flexible cord that contains six current-carrying conductors?
80 percent of the value.

318. What are the requirements, with respect to exposed live parts, on lighting fixtures?
There may be no live parts exposed, except on cleat receptacles and lamp holders that are located at least 8 feet above the floor.

 319. What must be done to flexible cords and cables where they pass through holes in covers, outlets boxes, or similar enclosures?
They require protection in the form of bushings or fittings.
 
320. Under what conditions may a light blue colored insulation is used for the identification of a grounded conductor in a flexible cord?
For jacketed cords furnished with an appliance.

321. Under what conditions may multiconductor cables rated at over 600 volts, nominal, be used?
To  connect mobile equipment and mobile machinery.
 
322. What precautions are necessary when installing fixture wires in temperatures colder than 10°C (14° F)?
Exercise care during installation, since the conductors may become brittle.
 
323. What is the maximum operating temperature of a Type TFFN fixture wire?
90 C.
 
324. What are the requirements for fixtures installed near combustible materials?
They must be constructed, installed, or equipped with shades or guards so that combustible materials won’t be subjected to temperatures in excess of 90 C (194 F).
 
325. Under what condition may a fixture is installed in a show window?
When it is chain-supported and externally wired.
 
326. When a fixture weighs more than 50 pounds, may it be sup- ported from the outlet box?
It must be supported independently of the outlet box.
 
327. What precautions must be taken in conductors for movable parts of fixtures?
Stranded conductors must be used and must be arranged so that the weight of the fixture or movable parts won’t put tension on the conductors. These measures must be taken to protect the conductors.
 
328. What types of insulation are permitted within 3 inches of a ballast within a ballast compartment? Conductors  rated  at  90 C  (194 F).

329. Which  wire  must  be  connected  to  the  screw  shells  of lampholders?
The grounded, or white, conductor.
 
330. What is the maximum wattage permitted on a medium lamp base?
300 watts.
 
331. What is the maximum lamp wattage permitted for a mogul lamp base?
1500 watts.
 
332. How must fixtures be grounded?
They may be connected to metal raceways, the armor of metal-clad cable, etc., if properly installed and grounded, or a separate equipment-grounding conductor not smaller than No. 14 wire may be used.
 
333. On motor-driven appliances, what disconnecting means must be provided, and how must it be located?
The switch or circuit breaker that serves as the disconnecting means on a stationary motor-driven appliance must be located within sight of the motor controller or be capable of being locked in the open position.

334. On all space-heating systems, what is the main requirement?
All heating equipment must be installed in an approved manner.
 
335. What are the requirements for heating cables? Heating  cables  must  be  supplied  complete  with  factory- assembled nonheating leads of at least 7 feet in length.
 
336. What markings must be present on heating cables?
Each unit length must have a permanent marking located within 3 inches of the terminal end of the nonheating leads, with the manufacturer’s name or identification symbol, catalog number, and the rating in volts and watts or amperes. The leads on a 240-volt cable must be red; on a 120-volt cable the leads are yellow; 208-volt cable leads are blue; and on a 277-volt cable the leads are brown.

337. What clearance must be given to wiring in ceilings?
Wiring above heated ceilings and contained within thermal insulation must be spaced not less than 2 inches above the heated ceiling and will be considered as operating at 50 C. Wiring above heated ceilings and located over thermal insulation having a minimum thickness of 2 inches requires no correction for temperature.  Wiring  located  within  a  joist  space  having  no  thermal insulation must be spaced not less than 2 inches above the heated ceiling and will be considered as operating at 50 C.
   
338. What are the restricted areas for heating?
Heating panels must not extend beyond the room or area in which they originate; cables must not be installed in closets, over cabinets that extend to the ceiling, under walls or partitions or over walls or partitions that extend to the ceiling.
 
339. What clearance must be provided for heating cables and panels from fixtures, boxes, and openings?
Panels and heating cables must be separated by a distance of at least 8 inches from lighting fixtures, outlets, and junction boxes, and 2 inches from ventilation openings and other such openings in room surfaces, or at least a sufficient area must be provided  340. May embedded cables be spliced? Only when absolutely necessary, and then only by approved means; in no case may the length of the cable be altered.
 
341. May heating cable be installed in walls?
No.
 
342. How  must  hermetic-type  refrigeration  compressors  be marked?
They  must  have  a  nameplate,  giving  the  manufacturer’s name, the phase, voltage, frequency, and full-load current in amperes of the motor current when the compressor is delivering the rated output. If the motor has a protective device, the name- plate  must  be  marked  “Thermal  Protection.”  For  complete details.

343. When using switches, fuses, and other disconnecting means, must the voltage of the switch coincide with that of the motor?
Yes. The voltage rating of the switch may not be less than 115 percent of the full load current rating of the motor.
 
344. If a switch is used that has a current rating larger than is required, may it be adapted for less current?
Yes, adapters of the approved type are available for reducing the fuse size of the switch; fuses larger than the switch rating, however, may not be used.

345. May  the  enclosures  for  controllers  and  disconnecting means for motors be used as junction boxes?
Enclosures for controllers and disconnecting means for motors may not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to the other apparatus unless designs are employed that provide adequate space for this purpose.
 
346. If a branch circuit supplies only one motor, how large must the conductor size of the branch circuit be in comparison to the cur- rent rating of the motor?
The branch-circuit conductors should be figured at not less than 125 percent of the full-load current rating of the motor.
 
347. How shall equipment for hazardous (classified) locations be marked?
Approved equipment shall be marked to show the class, group, and operating temperature or temperature range, based on operation in a 40 C ambient for which it is approved Exceptions are made for equipment of the nonheat-producing type, such as junction boxes, conduit, and fittings, which are not required to have a marked operating temperature.

348. What is a Class I location?
These are locations in which flammable gases or vapors are, or may be, present in the air in quantities sufficient to produce explosive or ignitable mixtures.
 
349. What is a Class I, Division 1 location?
Locations in which hazardous concentrations of flammable gases or vapors exist continuously, intermittently, or periodically under normal operating conditions; in which hazardous concentrations of such gases or vapors may exist frequently because of repair or maintenance operations or because of leakage; or in which breakdown or faulty operations of equipment or processes that might release hazardous concentrations of flammable gases or vapors might also cause simultaneous failure of electrical equipment.
 
350. What is a group A atmosphere in a hazardous (classified) location?
One that contains acetylene.
 
351. What is a group C atmosphere in a hazardous (classified) location?
One that contains cyclopropane, ethylether, ethylene, or gases or vapors of equivalent hazard 
352. What is intrinsically safe wiring and equipment? Equipment and wiring that is not capable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause ignition of a specific flammable or combustible atmospheric mixture in its most easily ignitable concentration.

353. What precautions must be taken when installing intrinsically safe circuits?
They are required to be physically separated from wiring of all other circuits that are not intrinsically safe and from separate intrinsically safe circuits.
 
354. What is a Class I, Division 2 location?
Locations in which flammable volatile liquids or flammable gases are handled, processed, or used, but in which the hazardous liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems, or in case of abnormal operation of equipment; in which hazardous concentrations of gases or vapors are normally prevented by positive mechanical ventilation, but which might become hazardous through failure or abnormal operation of the  ventilating equipment; or which are adjacent to a Class I, Division 1 location and to which hazardous concentrations of gases  or  vapors  might  occasionally  be  communicated  unless such communication is prevented by adequate positive-pressure ventilation from a source of clean air, and effective safeguards against ventilation failure are provided.
 
355. What are Class II locations?
Locations that are hazardous because of the presence of combustible dust.
 
356. What are Class II, Division 1 locations?
Locations in which combustible dust is, or may be, in suspension in the air continuously, intermittently, or periodically under normal operating conditions in quantities sufficient to produce explosive or ignitable mixtures; where mechanical failure or abnormal operation of machinery or equipment might cause such mixtures to be produced and might also provide a source of ignition through simultaneous failure of electrical equipment, operation of protective devices, or from other causes; or in which dusts of an electrical conducting nature may be present.
 
357. What are Class II, Division 2 locations?
Locations in which combustible dust won’t normally be in suspension in the air or is not likely to be thrown into suspension by the normal operation of equipment or apparatus in quantities sufficient to produce explosive or ignitable mixtures, but where deposits or accumulations of such dust may be sufficient to interfere with the safe dissipation of heat from electrical equipment and apparatus, or where such deposits or accumulations of dust on, in, or in the vicinity of electrical equipment might be ignited by arcs, sparks, or burning material from such equipment.
 
358. What are Class III locations?
Locations that are hazardous because of the pressure of easily ignitable fibers or flyings, but in which such fibers or flyings are not likely to be suspended in the air in quantities sufficient to produce ignitable mixtures.
 
359. What are Class III, Division 1 locations?
Locations in which easily ignitable fibers or materials producing combustible flyings are handled, manufactured, or used.

360. What are Class III, Division 2 locations?
Locations in which easily ignitable fibers are stored or handled, except in process or manufacture of the product.
 
361. Where may meters, instruments, and relays is mounted in Class I, Division 1 locations?
Within enclosures approved for this location.
 
362. Where may meters, instruments, and relays with make-and- break contacts be mounted in Class I, Division 2 locations? Immersed in oil or hermetically sealed against vapor or gases 
363. What type of wiring must be used in Class I, Division 1 areas?
Rigid metal conduit (threaded), intermediate metal conduit, or Type MI cable.

364. What type of fittings must be used in Class I, Division 1 areas?
All boxes, fittings, and joints must be threaded. At least five full threads must be used and must be fully engaged, and all materials,  including  flexible  connections,  must  be  approved (explosion-proof) by the inspecting authority for these locations.

14-25  What type of wiring must be used in Class I, Division 2 areas?
Threaded rigid metal conduit, threaded steel intermediate metal conduit, enclosed gasketed busways, or Type PLTC cable in accordance with the provisions of Article 725, Type MI, MC, MV, TC, or SNM cable with approved termination fittings.
 
365. What type of fittings must be used in Class I, Division 2 areas?
Only boxes, fittings, and joints that are approved for this location.
 
366. Why is sealing needed in conduit systems and not in Type MI cable systems in Class I areas? Seals are provided in conduit systems to minimize the pas- sage of gases, vapors, or fumes from one portion of the electrical.

367. When connecting conduit to switches, circuit breakers, etc., where must seals be placed?
As close as possible to the enclosure, but not more than 18 inches away.
 
368. When a conduit leaves a Class I, Division 1 location, where must the seal be located?
The seal must be placed at the first fitting when a conduit leaves this area; it may be on either side of the boundary.
 
369. When a conduit leaves a Class I, Division 2 location, where must the seal be located?
The seal must be placed at the first fitting when a conduit leaves this area; it may be on either side of the boundary.

 370. If there is a chance that liquid will accumulate at a seal, what precautions must be taken?
An approved seal for periodic draining of any accumulation must be provided.
 
371. What must be provided for switches, motor controllers, relays, fuses, or circuit breakers in Class I locations?
They must be provided with enclosures and must be approved for the location.
 
372. Is grounding necessary in Class I locations?
Yes. It is highly important. All exposed noncurrent-carrying parts of equipment are required to be grounded. Locknuts and bushings are not adequate grounding; they must have bonding jumpers around them. Where flexible conduit is used as permitted, bonding jumpers must be provided around such conduit.
 
373. Is surge protection required in Class I locations?
No, but if installed, lightning-protection devices are required on all ungrounded conductors. They must be connected ahead of the service-disconnecting means and must be bonded to the race- way at the service entrance.
 
374. What are some of the precautions that must be taken when transformers are used in Class II, Division 1 locations?
Transformers containing a flammable liquid must be installed only in approved vaults that are constructed so that a fire cannot be communicated to the hazardous area. Transformers that don’t contain a flammable liquid must also be installed in vaults or must be enclosed in tight metal housings without ventilation.
 
375. What type of wiring must be installed in Class II, Division 1 locations?
Rigid metal conduit (threaded), threaded steel intermediate metal conduit, or Type MI cable must be used. Boxes and fittings must have threaded bosses and tight-fitting covers and must be approved for the location.
 
376. What type of wiring must be installed in Class II, Division 2 locations?
Rigid metal conduit, intermediate metal conduit, dust-tight wireways, electrical metallic tubing, or Type MI, MC, or SNM cable. Boxes, fittings, and joints must be made to minimize the entrance of dust.
 
377. Is grounding and bonding necessary in Class II locations?
Yes. All exposed noncurrent-carrying parts of equipment must be grounded. Locknuts and bushings are not adequate grounding; they must use bonding jumpers.
 
378. Is surge protection required in Class II locations?
If installed, lightning-protection devices of the proper type are required on all ungrounded conductors; they must be connected ahead of the servicedisconnecting means and must be bonded to the raceway at the service entrance.
 
379. What type of wiring is required in Class III, Division 1 locations?
Threaded rigid metal conduit, threaded steel intermediate metal conduit, or Types MI, MC, SNM; boxes and fittings must have tight-fitting covers. There must not be any screw-mounting holes within the box through which sparks might escape.
 
380. What vehicles are included under the commercial-garages classification?
These locations include places of storage, repairing, or servicing of self-propelled vehicles, including passenger automobiles, buses,  trucks,  tractors,  etc.,  in  which  flammable  liquids  or flammable gases are used for fuel or power.

381. What is a gasoline-dispensing and service station?
This  includes  locations  where  gasoline  or  other  volatile flammable gases are transferred to the fuel tanks (including auxiliary fuel tanks) of self-propelled vehicles. Lubritoriums, service rooms, repair rooms, offices, sales-rooms, compressor rooms, and similar locations.
 
382. What types of conductors are typically found in a set of network-powered broadband cables? Coaxial, twisted-pair, fiber optic, and power conductors.
 
383. What is a fault protective device?
A device for a network-powered broadband system that is designed to protect people and equipment in the case of faults in the system.
 
16-1 Which is the primary article of the PEC governing data cabling? 
16-2 When data conductors enter buildings, how far must they be kept from power drops?
A minimum of 12 inches.
 
16-3 What is a “protector”?
A type of surge suppression device specifically designed for communication circuits.
 
16-4 What is the minimum size of grounding conductor for communication circuits?
No. 14 AWG.
 
16-5 Is firestopping required for data cables that pass through fire-resistant barriers?
Yes.
 
16-7 For structured cabling, what is the horizontal distance limit between closet and desktop?
100 meters.

16-8 What is the most widely used type of data cable?
Unshielded twisted pair, also known as UTP.

16-9 Must telecommunications test equipment be listed?
No,  A city block.
 
16-11  What types of distribution circuits don’t require protectors?
Underground circuits that are unlikely to contact power circuits.
 
16-12  How far must communication circuits be separated from lightning protection conductors?
6  feet,  but  exceptions  are  made  when  this  spacing  is “impractical.”

16-13  What  restriction  is  placed  on  the  installation  path  of  a grounding conductor for communication circuits?
That it be run in a straight line.
 
16-14  May a metal power service conduit serve as the grounding electrode conductor for a communication grounding system?
Yes. 

16-15  What part of a communications cable must be grounded?
The metallic sheath.

16-16  Where must a communications cable be grounded once it enters a building?
As close as possible to the point of entrance.

16-17  What option to grounding exists?
The interruption of the cable sheath with an insulating interrupting device.

16-18  When a protector is installed on a mobile home, what is the minimum size of conductor that it must be bonded with?
No. 12 AWG.
 
16-19  What rating of communication cable is designed for installation in plenums?
Type CMP.

16-20  What rating of communication cable is designed for installation in risers?
Type CMR.
 
16-21  What rating of communication cable is designed for installation under carpets?
Type CMUC.
 
16-22  May communications circuits share a raceway with a community antenna television system? Yes.
 
16-23  What types of communication cables may be installed in cable trays?
Types MPP, MPR, MPG, MP, CMP, CMR, CMG, and CM.

16-24  What is meant by the word “premises”?
A user property on the far side of the demarcation point.
 
16-25  How should CATV conductors be installed on power poles?
Below power conductors.
 
16-26  What part of a coaxial cable must be grounded?
The outer conductive sheath. 

16-27  What is the required clearance above a roof for a coaxial cable entering a building?
8 feet, with two exceptions.

16-28  If a grounding conductor for a coaxial system is run in metal conduit, what other requirement must be met?
Both ends of the raceway must be bonded to the grounding conductor, terminal, or electrode.
 
16-29  What types of conductors are typically found in a set of network-powered broadband cables? Coaxial, twisted-pair, fiber optic, and power conductors.

16-30  What is a fault protective device?
A device for a network-powered broadband system that is designed to protect people and equipment in the case of faults in the system.
 
16-32  May network-powered broadband cables be installed with messenger wire?
Yes.
 
16-33  What is the minimal clearance above roofs for network- powered broadband cables?
8 feet, with exceptions for garages, overhangs, and sloped roofs.

16-34  Are protectors required for network-powered broadband systems?
Yes.
 
16-35  What is the minimum size of grounding conductor that may be used for network-powered broadband systems?
No. 14 AWG.
 
16-36  May a power service enclosure serve as a grounding electrode for a network-powered broadband system?
Yes.
 
16-37  If separate electrodes are used for power system grounding and for network-powered broadband grounding, what is required?
The two electrodes must be bonded with a conductor of no less than No. 6 AWG. An exception is made for bonding at mobile homes, if the mobile home is supplied with power via cord and plug, or where the mobile home has no service equipment or disconnecting means.
 
16-38  What is the maximum permitted length for Type BLX cable?
50 feet.
 
16-39  What types of network-powered broadband cables may be installed in plenum areas?
Type BLP. Type BLX is also acceptable, provided that it is installed according to the requirements of  PEC.

16-40  What are the maximum and minimum sizes of Type ITC cable conductors?
A minimum of No. 22 AWG and a maximum of No. 12 AWG are permitted for Instrumentation Tray Cables.

16-41  Why are optical fiber cables preferable to copper conductors for communications?
Because they can carry many times as many signals, with far less degradation of the signals. One pair of optical fiber cables can carry thousands of telephone conversations with better clarity and requiring far fewer amplifiers along its path.

16-42  What are the three basic parts of optical fiber cables?
The core, the cladding, and the outer covering.

16-43  What are the two most important things to remember when installing optical fiber cables? First, that the pulling force should not be applied to the optical fiber, but to a “strength member.” Second, that optical fiber cables cannot be sharply bent.

16-44  What is the most difficult operation of connecting optical fiber cables?
Terminating or splicing them. This can be a time-consuming and difficult process.

16-45  Optical fiber cables don’t carry electricity. Why are they covered within the PEC?
For two reasons: first, because they are often installed with electrical cables and by the same installers; second, because they are dependent upon the electrical and electronic equipment to which they are connected.

16-46  Does the PEC cover all optical fiber installations?
No. 

16-47  Can optical fiber cables be installed in cable trays?
Yes.
 
16-48  What types of optical fiber cables are allowed in plenums?
Types OFNP and OFPC. Also, if installed according to the rules of PEC, OFNR, OFCR, OFN, OFNG, OFC, and OFCG  may  also  be  installed  in  plenums.
 
16-49  What does the term photovoltaic mean?
Generating electricity from light.

16-50  What is a photovoltaic cell?
A special type of semiconductor that generates a small volt- age when exposed to light, generally about one half volt.

16-51  What type of electricity do photovoltaic cells generate?
Direct current only.

16-52  What is an array?
An assembly of photovoltaic panels.
 
16-53  Why are blocking diodes required for photovoltaic systems?
To prevent battery currents from flowing backward through the photovoltaic cells when no sunlight is present.

16-54  Do photovoltaic systems require special disconnects?
Yes. A disconnecting means must be installed that will disconnect photovoltaic conductors from all other system conductors.
 
16-55  Can any recognized type of wiring be used for photovoltaic systems?
Yes.
 
16-56  Must a 12-volt photovoltaic system be grounded?
No.
 
16-57  Name two types of communications signals.
Analog and digital.

16-58  In general, what type of signal is better?
Digital; it provides a much clearer and stronger signal.

16-59  What is a protector?
Protectors are surge-suppressor-type devices. They are required  for  many  outdoor  communication  circuits 

16-60  What is the smallest grounding conductor that can be used for communication circuits?
No. 14 copper.
 
16-61  What steps must be taken when communication grounding conductors are installed in metal conduit?
The metal conduit must be bonded on both ends.
 
16-62  Should communication grounds be bonded to power system grounds?
Yes.
 
16-63  How far must communication circuits be separated from power circuits?
At least 2 inches.
 
16-64  In what part of the PEC would you find requirements for fire alarm systems and circuits?

16-65  What is a closed-loop system?
A special type of power distribution that is controlled jointly by signals from the controlling equipment and the utilization equipment.

16-66  What types of disconnects are required in data processing areas?
They require a disconnect for all electronic equipment in these areas. In addition, there must be another disconnect for all HVAC equipment in these areas. These can be combined into one unit.

16-67  Are ventilated underfloor areas in computer rooms exempted from the special air-handling area requirements PEC?
Yes.
 
16-69  Conductors from a television antenna to a building must be kept how far from a 120/240 electrical service?
2 feet.
 
16-70  How far apart must supports for antenna cables be placed?
No specific distance is mentioned in the Code, just that they must be made secure.
 
16-71  What size conductor is required to connect a communications grounding electrode and a power grounding electrode?
At least No. 6 AWG copper.
 
16-72  Which article of the Code covers cable television systems?
Article 820 covers all such systems that are wired in coaxial cable, as almost all cable TV systems are.

16-74  How far must coaxial cables be kept from the conductors of lighting systems?
6 feet.
 
16-75  What size conductor is required to connect a television system grounding electrode and a power grounding electrode?
At least No. 6 AWG copper.
 
16-76  Which conductor of a coaxial cable can be grounded?
When the cable is to be grounded, it is the outer conductor that is connected to ground.
 
16-77  What types of coaxial cables may be run as risers in a building?
Types CATVP. Types CATVR, MPP, CMP, MPR, and CMR may be used if installed according to PEC.
 
16-80  What is the minimum size of conductor that can be used to interconnect storage batteries?
No. 2/0 AWG copper.