Ampere Rating Wire Copper Capacity Table
AWG Size | Metric (MM²) | THW Ampacity (75°C Maximum Operating Temperature) | THHN Ampacity (90°C Maximum Operating Temperature) | Breaker Capacity | Load Allowed (80%) |
---|---|---|---|---|---|
14 | 2.08 | 20 | 25 | 15A | 12A |
12 | 3.31 | 25 | 30 | 20A | 16A |
10 | 5.26 | 35 | 40 | 30A | 24A |
8 | 8.37 | 50 | 55 | 50A | 40A |
6 | 13.30 | 65 | 75 | 65A | 52A |
4 | 21.20 | 85 | 95 | 85A | 68A |
3 | 26.70 | 100 | 115 | 100A | 80A |
2 | 33.60 | 115 | 130 | 125A | 100A |
1 | 42.40 | 130 | 150 | 150A | 120A |
1/0 | 53.50 | 150 | 170 | 175A | 140A |
2/0 | 67.40 | 175 | 195 | 200A | 160A |
3/0 | 85.00 | 200 | 225 | 225A | 180A |
4/0 | 107.20 | 230 | 260 | 250A | 200A |
250 kcmil | 127.00 | 255 | 290 | 300A | 240A |
300 kcmil | 152.00 | 285 | 320 | 350A | 280A |
350 kcmil | 177.00 | 310 | 350 | 400A | 320A |
400 kcmil | 203.00 | 335 | 380 | 450A | 360A |
500 kcmil | 253.00 | 380 | 430 | 500A | 400A |
600 kcmil | 304.00 | 420 | 475 | 600A | 480A |
700 kcmil | 355.00 | 460 | 520 | 700A | 560A |
750 kcmil | 380.00 | 475 | 535 | 750A | 600A |
800 kcmil | 405.00 | 490 | 555 | 800A | 640A |
900 kcmil | 456.00 | 520 | 585 | 900A | 720A |
1000 kcmil | 507.00 | 545 | 615 | 1000A | 800A |
- AWG Size:
- American Wire Gauge, a standard for wire diameters.
- Smaller numbers mean thicker wires.
- Metric (MM²):
- The cross-sectional area of the wire in square millimeters.
- Cross-sectional area in metric units, useful for international applications.
- THW Ampacity (75°C):
- Applications: Dry and Wet Locations.
- The current carrying capacity of copper wire with THW (Thermoplastic Heat and Water resistant) insulation at 75°C.
- THHN Ampacity (90°C):
- Applications: Dry and Damp Locations.
- The current carrying capacity of copper wire with THHN (Thermoplastic High Heat-resistant Nylon-coated) insulation at 90°C.
- Breaker Capacity:
- The typical breaker size for the given wire size.
- The recommended breaker size for protecting the wire.
- Load Allowed (80%):
- The maximum recommended continuous load on the circuit, calculated as 80% of the breaker capacity, in accordance with PEC guidelines.
- The safe continuous load limit ensures the circuit does not overheat.
Explanation of the Ampere Rating Wire Copper Capacity Table
The table provided gives a comprehensive overview of the current-carrying capacity, or ampacity, of copper wires of different sizes, measured in American Wire Gauge (AWG) and their equivalent in square millimeters (MM²). It also provides ampacity ratings for wires with THW and THHN insulation types, the recommended breaker sizes, and the allowed continuous load for each wire size. Here’s a detailed explanation of each column and its significance:
Columns and Their Meanings:
- AWG Size:
- Definition:
American Wire Gauge (AWG) is a standard way of denoting wire diameter. Smaller AWG numbers indicate thicker wires. - Example:
14 AWG is thinner than 10 AWG.
- Definition:
- Metric (MM²):
- Definition:
This column represents the cross-sectional area of the wire in square millimeters, a metric measurement equivalent to AWG. - Example:
14 AWG is approximately 2.08 mm².
- Definition:
- THW Ampacity (75°C):
- Definition:
The maximum current (in amperes) that a wire with THW (Thermoplastic Heat and Water resistant) insulation can safely carry at 75°C ambient temperature. - Example:
A 14 AWG wire with THW insulation can carry 20 amperes.
- Definition:
- THHN Ampacity (90°C):
- Definition:
The maximum current a wire with THHN (Thermoplastic High Heat-resistant Nylon-coated) insulation can carry at 90°C ambient temperature. - Example:
A 14 AWG wire with THHN insulation can carry 25 amperes.
- Definition:
- Breaker Capacity:
- Definition:
The recommended size of the circuit breaker that should be used to protect the wire. This ensures the wire does not overheat and cause a fire. - Example:
For a 14 AWG wire, a 15-ampere breaker is recommended.
- Definition:
- Load Allowed (80%):
- Definition:
To ensure safety and reliability, continuous loads on a circuit should not exceed 80% of the breaker’s capacity. This column lists the maximum allowed continuous load for each breaker. - Example:
For a 15-ampere breaker, the maximum continuous load is 12 amperes (80% of 15A).
- Definition:
Usage Considerations:
- Ampacity:
- This indicates the maximum current a wire can handle before overheating. THHN has a higher ampacity than THW due to its higher temperature rating.
- Breaker Capacity:
- Electrical codes recommend using a breaker that is appropriately rated for the wire size to prevent overheating and potential fire hazards.
- Load Allowed:
- Continuous loads should not exceed 80% of the breaker capacity to ensure safety and longevity of the electrical system.
Practical Application:
- Wire Sizing for Circuits:
- When planning electrical circuits, choose the wire gauge based on the expected load and distance to prevent voltage drop and overheating.
- Purpose:
Selecting the correct wire size ensures that the wire can handle the expected electrical load without overheating. - Example:
If a circuit requires carrying 24 amperes, you should choose a wire gauge that supports this current. According to the table, a 10 AWG wire with THHN insulation is suitable.
- Breaker Selection:
- Ensure the breaker is rated appropriately for the wire gauge to protect the circuit from overcurrent conditions.
- Purpose:
A properly sized breaker protects the wire and prevents potential fire hazards by interrupting the circuit if the current exceeds safe levels. - Example:
For a 10 AWG wire, a 30-ampere breaker is recommended.
- Load Management:
- Purpose:
To prevent overloading the circuit, ensure that continuous loads do not exceed 80% of the breaker’s capacity. This margin helps avoid overheating and ensures the longevity of the electrical system. - Example:
For a 30-ampere breaker, the continuous load should not exceed 24 amperes.
- Purpose:
- Compliance with Codes:
Adhering to the Philippine Electrical Code (PEC) is crucial for safety and legal compliance.
IMPORTANT NOTICE:
Before taking any actions in your Electrical Installations if you are unsure or not qualified or trained to do Electrical works always consult a Licensed Electrical Practitioner, Professional Electrical Engineer (PEE), Registered Electrical Engineer (REE), or Registered Master Electrician (RME).